Home >> Case >> Cooperation Cases>> Qingdao Nanke Electric International Electrical Co., Ltd. and Wuxi Yineng Power Equipment Co., Ltd. cooperate (2)

Qingdao Nanke Electric International Electrical Co., Ltd. and Wuxi Yineng Power Equipment Co., Ltd. cooperate (2)

【Introduction】Wuxi Yineng Power Equipment Co., Ltd. Semi-Automatic Transformer Intelligent Testing System 2025, Eighth Intelligent Testing Station (Part II): Offline Large-Capacity Three-Phase Transformer Intelligent Testing System
【Keywords】

1. Project Overview

This project is custom-designed by Nanke Electric for Wuxi Yineng Power, and it belongs to the second part of their 2025 eighth intelligent test station. It is an offline large-capacity three-phase transformer intelligent testing system capable of completing all factory acceptance tests for oil-immersed and dry-type transformers up to 25 MVA. This system is suitable for offline large-capacity testing scenarios, meeting the factory quality control requirements for high-capacity transformers in fields such as rail transit, power transmission and distribution, and new energy, thereby helping customers achieve intelligent and standardized testing.


2. Maximum Testing Capacity

Offline Large-Capacity Test Area for Oil-Immersed/Dry-Type Transformers: Transformer capacity: 25,000 kVA; Primary voltage: 35.00 kV; Secondary voltage: 0.4–10.00 kV; Short-circuit impedance: 6.00%–14.00%;

Transformer capacity: 16,000 kVA; Primary voltage: 20.00 kV; Secondary voltage: 2 kV and below; Short-circuit impedance: 6.00%–10.00%;

Transformer capacity: 6,300 kVA; Primary voltage: 10.00 kV; Secondary voltage: 2 kV and below; Short-circuit impedance: 10% and below.

3. Test Items

1. Insulation resistance test;

2. DC resistance test;

3. Turns ratio and connection group test;

4. No-load test: no-load loss, power factor measurement, and no-load current percentage test;

5. Load test: load loss (automatically converted to values at 75°C, 120°C, and 145°C), short-circuit impedance percentage;

6. Induced withstand voltage test;

7. Power frequency withstand voltage test;

8. Temperature rise test;

9. Partial discharge test;

10. Sound level measurement.

4. Project Highlights

Full Coverage of Large Capacities: Supports comprehensive testing for oil-immersed and dry-type transformers up to 25 MVA, compatible with multiple voltage levels up to 35 kV, meeting the needs of large-capacity testing.

One-Stop Comprehensive Testing: Covers 10 core test items, enabling complete factory acceptance testing in a single session without requiring separate setups or scenario-based testing.

Intelligent and Efficient: Automatically converts load loss values across multiple temperature points, eliminating manual calculations, ensuring precise and compliant data, and significantly improving testing efficiency.

Adapted for Offline Scenarios: Specifically designed for offline large-capacity test areas, featuring a well-planned layout and convenient operation that aligns with on-site testing workflows.

Mature Delivery: Leveraging proven technical solutions, rapid customized implementation, and providing integrated services including installation, commissioning, and training.

5. Commissioning Information

Client: Wuxi Yineng Power Equipment Co., Ltd.

Commissioning Date: March 2026

Commissioning Date: April 2026